Data Center Filtration: Micron Ratings by Cooling Loop

Short answer

A data center liquid-cooling (TCS / CDU secondary) loop is typically filtered at about 25 µm inline, with ≤50 µm acceptable and a finer side-stream under 5 µm. Facility water into the CDU is strained at about 100–500 µm, with OCP listing a primary filter at ≤200 µm, and OCP asks for makeup water filtered to 1 µm where possible. The equipment maker's spec always governs.

Quick reference

Published micron guidance by data center cooling loop
LoopPublished micron guidanceSource
TCS / CDU secondary (cold plates)≤25 µm for microchannel cold plates; 25/50 µm inline; side-stream <5 µmOCP Modular TCS Rev 1; OCP L2L CDU methodology
CDU secondary loop filter (example datasheet)25 µm standard, 50 µm optional, with ΔP clog detectionRittal CDU In-Rack datasheet
Endpoint filtration without CDU≤100 µmASHRAE TC9.9 white paper
Facility water system (FWS)Primary ≤200 µm (OCP); 100–500 µm strainers (Eaton)OCP; Eaton
Cooling tower side-streamCartridges 5–50 µm, bags 5–75 µmFil-Trek; DOE FEMP
Makeup water1 µm where possibleOCP Modular TCS Rev 1
Flush / commissioning5–50 µm cartridges or bagsFil-Trek

Questions and answers

What micron filter does a CDU secondary loop need?

OCP documents describe 25–50 µm as typical for the TCS loop. Microchannel cold plates call for ≤25 µm, plus side-stream polishing below 5 µm. The cold-plate or CDU maker's spec is the deciding requirement.

What's the difference between nominal and absolute ratings?

A nominal rating means the filter captures a share of particles at that size. An absolute or beta-ratio rating (ISO 16889, cited by ASHRAE TC9.9) is a tested capture efficiency. Liquid cooling specs often call for absolute or beta ratings. Each FilterBridge product page gives the rating type the manufacturer publishes.

Do you sell filters rated for CDU coolant loops?

Send us your filter spec (micron rating and rating basis, cartridge size, media, fluid, temperature and flow) and we'll quote to it, usually within one business day.

What filtration is used on the facility water side?

Strainers, typically 100–500 µm. OCP lists a primary filter at ≤200 µm.

What micron for cooling tower side-stream?

Cartridges about 5–50 µm (bags about 5–75 µm), on 3–10% of flow (up to 20%) per DOE FEMP. See the side-stream guide.

How fine should makeup water be filtered?

OCP's Modular TCS document says 1 µm where possible. Many sites also use RO for makeup or humidification. See commercial RO pretreatment.

What micron is used for flushing new loops?

Typically 5–50 µm cartridges or bags, stepping finer as the system cleans up. See the system flush guide.

When should filters be changed?

At the differential pressure limit your system specifies. One published cold-plate example sets a side-stream alarm around 1.5 psi (DLB Associates, 2025). Follow your own system's limit.

Who sets the final spec?

The cooling equipment maker and the engineer of record. This guide summarizes public guidance and doesn't replace either.